YOKOGAWA – Analog I/O Modules (for FIO) RTD /POT INPUT – P/N: AAR145-S50 S1

2 in stock

WhatsApp Contact Button WhatsApp Icon Get Quote

The AAR145-S50-S1 is a high-precision analog input module designed for Yokogawa’s Field I/O (FIO) systems, supporting RTD (Resistance Temperature Detector) and potentiometer signals. It integrates seamlessly with CENTUM VP and ProSafe-RS control systems for accurate temperature and position monitoring.

 

SKU: YOKO-AAR145S50S1

 

Price:

Key Features:

Signal Compatibility

  • RTD Types:
    • Pt100, JPt100, Ni120, Cu10 (2-wire/3-wire/4-wire configurations)
    • Supports linearization for non-standard RTDs
  • Potentiometer Input:
    • 0–500Ω, 0–1kΩ, 0–2kΩ ranges
    • Used for valve position feedback, level sensors, etc.

Performance

  • Channels: Configurable per module (e.g., 8-channel RTD or mixed RTD/potentiometer)
  • Accuracy: ±0.1% of span (typical for RTD inputs)
  • Update Rate: <100 ms per channel (varies by configuration)

Integration & Diagnostics

  • Compatibility:
    • Works with FIO Field Control Units (e.g., AFV30D, A2FV50S)
    • Supports CENTUM VP Engineering Studio for configuration
  • Hot-Swappable: Replace without system shutdown (redundant systems only)
  • Diagnostics:
    • Open-circuit detection for RTDs
    • Over-range/under-range alarms

Physical & Environmental

  • IsolationNon-isolated (common reference for all channels)
  • Operating Temperature: -20°C to +70°C
  • Certifications: Complies with IEC 61131-2 for industrial environments

Ordering & Suffix Codes

Suffix Description
-S50 Standard FIO version
-S1 Hardware revision (Style 1)
-E Explosion-proof variant (e.g., AAR145-S50-E)

Note:

  • For isolated RTD inputs, consider the AAR143 series.
  • Verify Style S1 compatibility with your system firmware.

Typical Applications

  • Temperature Monitoring: Tanks, pipelines, reactors (via RTDs)
  • Valve Positioning: Feedback from potentiometer-equipped actuators
  • Safety Systems: Integration with ProSafe-RS for critical measurements

Installation & Wiring

  1. Slot Assignment: Install in FIO I/O unit slots (refer to FCU manual).
  2. Wiring:
    • RTDs: Use twisted/shielded cables for noise immunity.
    • Potentiometers: Ensure proper grounding to avoid signal drift.
  3. Configuration:
    • Set RTD type/range via CENTUM VP Engineering Studio.
    • Calibrate using Yokogawa’s Field Device Management (FDM).

 

SKU: YOKO-AAR145S50S1