YOKOGAWA – ESB Bus Interface Master Module Revision VH 21 F1 F2 S90440DL-00 – PART NUMBER: SB 301 STYLE S1

2 in stock

WhatsApp Contact Button WhatsApp Icon Get Quote

The SB301-S1 is an ESB (Enhanced Serial Backplane) Bus Master Module for Yokogawa’s CENTUM VP and ProSafe-RS control systems. It serves as the primary communication interface between the Field Control Station (FCS) and I/O nodes via the high-speed ESB bus.

SKU: YOKO-SB301STYLES1

 

Price:

Key Features

1. Communication & Performance

  • RoleMaster module for ESB Bus (controls data exchange with slave modules)
  • Protocol: Yokogawa’s proprietary ESB protocol
  • Transmission Speed128 Mbps (deterministic real-time communication)
  • Redundancy: Supports dual-redundant ESB bus configurations
  • Max Nodes: Up to 9 I/O units (e.g., ANB10D, ANT401)

2. Hardware Specifications

  • RevisionVH21 (firmware/hardware version)
  • StyleS1 (compatible with legacy systems)
  • Part MarkingS90440DL-00 (manufacturing code)
  • Connectors: ESB ports for daisy-chaining I/O modules
  • LED Indicators: Power, communication status, faults

3. Compatibility

  • Works With:
    • FIO (Field I/O) Units: AFV30D, AFV40S, A2FV50D
    • Processor Modules: CP471 (requires Style S1 or later)
    • CENTUM VP Versions: R4.x to R6.x (verify firmware compatibility)

4. Environmental & Certifications

  • Operating Temp.-20°C to +70°C
  • CertificationsCEIEC 61131-2 (industrial EMC/immunity)

Part Number Breakdown

Segment Description
SB301 ESB Bus Master Module
-S1 Style 1 hardware revision
VH21 Firmware/board revision
F1/F2 Factory configuration codes
S90440DL-00 Yokogawa internal manufacturing ID

Note:

  • For non-redundant systems, install in Slot 7 of the FCU.
  • For redundant setups, install a second SB301 in Slot 8.

Installation & Wiring

  1. Slot Assignment:
    • Non-redundant: Slot 7 (Slot 8 must be covered with a dummy module).
    • Redundant: Slots 7 & 8 (both modules active).
  2. ESB Cabling:
    • Use shielded twisted-pair cables (max 10m per segment).
    • Terminate bus ends with 50Ω resistors.
  3. Grounding:
    • Ensure proper chassis grounding (<10Ω impedance).

Diagnostics & Troubleshooting

  • Fault LEDs: Check for:
    • PWR: Power failure (verify 24V DC supply).
    • COM: ESB bus communication errors (check termination/cabling).
  • Engineering Tools: Use CENTUM VP Engineering Studio to monitor ESB bus health.

 

SKU: YOKO-SB301STYLES1