Description
Key Features:
Signal Compatibility
- RTD Types:
- Pt100, JPt100, Ni120, Cu10 (2-wire/3-wire/4-wire configurations)
- Supports linearization for non-standard RTDs
- Potentiometer Input:
- 0–500Ω, 0–1kΩ, 0–2kΩ ranges
- Used for valve position feedback, level sensors, etc.
Performance
- Channels: Configurable per module (e.g., 8-channel RTD or mixed RTD/potentiometer)
- Accuracy: ±0.1% of span (typical for RTD inputs)
- Update Rate: <100 ms per channel (varies by configuration)
Integration & Diagnostics
- Compatibility:
- Works with FIO Field Control Units (e.g., AFV30D, A2FV50S)
- Supports CENTUM VP Engineering Studio for configuration
- Hot-Swappable: Replace without system shutdown (redundant systems only)
- Diagnostics:
- Open-circuit detection for RTDs
- Over-range/under-range alarms
Physical & Environmental
- Isolation: Non-isolated (common reference for all channels)
- Operating Temperature: -20°C to +70°C
- Certifications: Complies with IEC 61131-2 for industrial environments
Ordering & Suffix Codes
| Suffix | Description |
|---|---|
| -S50 | Standard FIO version |
| -S1 | Hardware revision (Style 1) |
| -E | Explosion-proof variant (e.g., AAR145-S50-E) |
Note:
- For isolated RTD inputs, consider the AAR143 series.
- Verify Style S1 compatibility with your system firmware.
Typical Applications
- Temperature Monitoring: Tanks, pipelines, reactors (via RTDs)
- Valve Positioning: Feedback from potentiometer-equipped actuators
- Safety Systems: Integration with ProSafe-RS for critical measurements
Installation & Wiring
- Slot Assignment: Install in FIO I/O unit slots (refer to FCU manual).
- Wiring:
- RTDs: Use twisted/shielded cables for noise immunity.
- Potentiometers: Ensure proper grounding to avoid signal drift.
- Configuration:
- Set RTD type/range via CENTUM VP Engineering Studio.
- Calibrate using Yokogawa’s Field Device Management (FDM).
SKU: YOKO-AAR145S50S1








Reviews