YOKOGAWA – Analog Input Module4-20mA 16 ch non iso. AAI141-S2

1 in stock

WhatsApp Contact Button WhatsApp Icon Get Quote

The AAI141-S2 is a 16-channel analog input module for Yokogawa’s CENTUM VP and ProSafe-RS control systems. It accepts 4-20mA current signals from field devices (e.g., sensors, transmitters) and converts them into digital data for process monitoring and control.

SKU: YOKO-AAI141S2 

Price:

 

Key Features

Signal Input

  • Type: 16 channels of 4-20mA DC current input (non-isolated)
  • Resolution16-bit analog-to-digital conversion
  • Accuracy: ±0.1% of full scale (typical)
  • Sampling Rate: Configurable per channel (e.g., 10–100 ms update time)

Compatibility & Integration

  • System Compatibility:
    • Works with FIO (Field I/O) units (e.g., AFV30D, A2FV50S)
    • Integrates with CENTUM VP DCS and Engineering Windows (EWS)
  • Hot-Swappable: Supports online replacement in redundant configurations
  • Wiring:
    • Terminal block connections for field devices
    • Supports HART communication (if enabled in firmware)

Diagnostics & Protection

  • Fault Detection: Open wire, over-range, under-range, and signal drift alarms
  • LED Indicators: Per-channel status (active, fault, communication)
  • Noise Immunity: Shielded terminal design for EMI/RFI protection

Environmental & Mechanical

  • Operating Temperature-20°C to +70°C
  • IsolationNon-isolated (all channels share a common ground)
  • Certifications: Complies with IEC 61131-2 for industrial use

Suffix Code Breakdown (AAI141-S2)

Suffix Description
-S2 Hardware revision (Style 2)
-E Explosion-proof variant (e.g., AAI141-S2-E)

Note:

  • For isolated 4-20mA inputs, use the AAI143 series.
  • Non-isolated design requires careful grounding to avoid noise interference.

Typical Applications

  • Process Monitoring: Pressure, flow, level, and temperature transmitters
  • Batch Control: High-density analog signal acquisition
  • Safety Systems: Integration with ProSafe-RS for critical measurements

Installation & Configuration

  1. Slot Assignment: Install in FIO I/O unit slots (refer to FCU manual).
  2. Wiring:
    • Use shielded twisted-pair cables for noise reduction.
    • Ensure proper grounding to avoid ground loops.
  3. Configuration:
    • Set input ranges and alarms via CENTUM VP Engineering Studio.
    • Calibrate using Yokogawa’s Field Device Manager (FDM).

 

SKU: YOKO-AAI141S2